DocumentCode
1988851
Title
A frequency response technique to allocate FACTS devices
Author
Ramirez, Juan M. ; Coronado, Ixtlahuatl
Author_Institution
CINVESTAV-UNIDAD, Guadalajara, Mexico
Volume
3
fYear
2001
fDate
15-19 July 2001
Firstpage
1530
Abstract
In this paper a technique based on open and closed-loop frequency response is proposed to allocate FACTS devices. On those devices with more than one control input, the best one can be selected in order to get the major damping over specific electromechanical modes. The technique is exemplified on a 46-machine power system and a comparison is made with a method based on residues, obtaining similar results.
Keywords
damping; flexible AC transmission systems; frequency response; load flow control; power system control; power system stability; thyristor applications; 46-machine power system; FACTS devices allocation; TCSC damping controller; UPFC; closed-loop frequency response; control input; damping; electromechanical modes; power system control; power system stability; Control systems; Controllability; Costs; Damping; Frequency response; Power system control; Power system stability; Power system transients; Power systems; Voltage control;