  • Abstract
    In this paper a technique based on open and closed-loop frequency response is proposed to allocate FACTS devices. On those devices with more than one control input, the best one can be selected in order to get the major damping over specific electromechanical modes. The technique is exemplified on a 46-machine power system and a comparison is made with a method based on residues, obtaining similar results.
  • Keywords
    damping; flexible AC transmission systems; frequency response; load flow control; power system control; power system stability; thyristor applications; 46-machine power system; FACTS devices allocation; TCSC damping controller; UPFC; closed-loop frequency response; control input; damping; electromechanical modes; power system control; power system stability; Control systems; Controllability; Costs; Damping; Frequency response; Power system control; Power system stability; Power system transients; Power systems; Voltage control;