    Inverse time overcurrent protection scheme for fault location in multi-terminal HVDC

  • Author

    Torres-Olguin, Raymundo E. ; Hoidalen, Hans Kristian

  • Author_Institution
    Department of Electric Power Engineering, Norwegian University of Science and Technology NTNU, Trondheim, Norway
  • fYear
    2015
  • fDate
    June 29 2015-July 2 2015
  • Firstpage
    1
  • Lastpage
    6
  • Abstract
    One of the main challenges with HVDC multi-terminal (MTDC) configurations, which are based on voltage source converters (VSC), is the protection system. The dc grids have small series inductances which made them unable to limit the rise time of the DC current when a dc fault occurs. For this reason, the dc fault clearing must be performed very fast in order to limit the effect of the rapid increase of the dc current during dc faults. However, before clearing the line, the fault must be detected and located as soon as possible. The fault location is very challenging using conventional methods that have been used in ac system. This paper investigates a fault location algorithm based on inverse-time overcurrent characteristic. In this algorithm the protection operating time is inversely changed with the current magnitude, so in order to implement it, feed inductor at each cable terminal is needed. A simplified version of CIGRE B4 DC Grid Test System is implemented in PSCAD to test the proposed algorithm.
  • Keywords
    Circuit faults; Fault location; HVDC transmission; Inductors; Power cables; Relays; Transmission line measurements; Fault location; Fault protection; HVDC transmission; PSCAD;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    PowerTech, 2015 IEEE Eindhoven
  • Conference_Location
    Eindhoven, Netherlands
  • Type

    conf

  • DOI
    10.1109/PTC.2015.7232673
  • Filename
    7232673