Inverse time overcurrent protection scheme for fault location in multi-terminal HVDC
Author
Torres-Olguin, Raymundo E. ; Hoidalen, Hans Kristian
Author_Institution
Department of Electric Power Engineering, Norwegian University of Science and Technology NTNU, Trondheim, Norway
fYear
2015
fDate
June 29 2015-July 2 2015
Firstpage
1
Lastpage
6
Abstract
One of the main challenges with HVDC multi-terminal (MTDC) configurations, which are based on voltage source converters (VSC), is the protection system. The dc grids have small series inductances which made them unable to limit the rise time of the DC current when a dc fault occurs. For this reason, the dc fault clearing must be performed very fast in order to limit the effect of the rapid increase of the dc current during dc faults. However, before clearing the line, the fault must be detected and located as soon as possible. The fault location is very challenging using conventional methods that have been used in ac system. This paper investigates a fault location algorithm based on inverse-time overcurrent characteristic. In this algorithm the protection operating time is inversely changed with the current magnitude, so in order to implement it, feed inductor at each cable terminal is needed. A simplified version of CIGRE B4 DC Grid Test System is implemented in PSCAD to test the proposed algorithm.
Keywords
Circuit faults; Fault location; HVDC transmission; Inductors; Power cables; Relays; Transmission line measurements; Fault location; Fault protection; HVDC transmission; PSCAD;
fLanguage
English
Publisher
ieee
Conference_Titel
PowerTech, 2015 IEEE Eindhoven
Conference_Location
Eindhoven, Netherlands
Type
conf
DOI
10.1109/PTC.2015.7232673
Filename
7232673
Link To Document