• DocumentCode
    2000111
  • Title

    Analysis of the instability of PFC power supplies with various AC sources

  • Author

    Hoff, C. Michael ; Mulukutla, Sarma

  • Author_Institution
    American Power Conversion Corp., Billerica, MA, USA
  • fYear
    1994
  • fDate
    13-17 Feb 1994
  • Firstpage
    696
  • Abstract
    Certain AC sources and line conditioners are not compatible with all power factor corrected (PFC) power supplies. The resulting combination can lead to system instability and cause complete loss of power control. The mathematical models of different types of AC sources and of a typical PFC power supply are presented and the interaction between them is described both qualitatively and in terms of stability requirements. Examples of unstable systems are shown and solutions to the stability problem from both ends of the power cord are discussed
  • Keywords
    power control; power factor correction; power supplies to apparatus; power system control; power system measurement; power system stability; AC sources; instability; interaction; line conditioners; mathematical models; power control; power cord; power factor correction; power supplies; unstable power systems; Frequency; Impedance; Power control; Power supplies; Pulsed power supplies; Reactive power; Resistors; Stability; Switched-mode power supply; Voltage;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Applied Power Electronics Conference and Exposition, 1994. APEC '94. Conference Proceedings 1994., Ninth Annual
  • Conference_Location
    Orlando, FL
  • Print_ISBN
    0-7803-1456-5
  • Type

    conf

  • DOI
    10.1109/APEC.1994.316330
  • Filename
    316330