Title :
Split-phase ground capacity measuring method for 10–35kV neutral point indirect earth system
Author :
Hou, Chong-Sheng
Author_Institution :
Inf. & Control Eng. Coll., Weifang Univ., Weifang, China
Abstract :
10-35 kV voltage grade power system, generally based on the size of single-phase current to the ground capacitor, arc overvoltage is prevented, so split-phase ground capacitor size for neutral point indirect earth system needs to be measured. The measuring method of split-phase ground capacity for neutral point indirect earth system by bias capacitor is introduced, and computing formula has been analyzed and observed; actual system parameters are incorporated into the formula, compared with the test data, proves that the method is simple and accurate numerical calculation, uninterrupted power supply to its customers and has broad prospects for application.
Keywords :
overvoltage protection; power capacitors; uninterruptible power supplies; arc overvoltage; bias capacitor; indirect Earth system; neutral point; single-phase current; split-phase ground capacitor; split-phase ground capacity; uninterrupted power supply; voltage 10 kV to 35 kV; voltage grade power system; Capacitance; Capacitance measurement; Earth; Frequency measurement; Grounding; Phase measurement; Voltage measurement; bias capacitor; ground capacitor; measurement;
Conference_Titel :
Electrical and Control Engineering (ICECE), 2011 International Conference on
Conference_Location :
Yichang
Print_ISBN :
978-1-4244-8162-0
DOI :
10.1109/ICECENG.2011.6058341