Abstract :
In this paper ten control strategies are tested, starting from a default tuning of the controllers, to evaluate its results in terms of general plant performance indicators such as the effluent quality index (EQI) and the operating cost index (OCI). Using the Benchmark simulation No 1 (BSM1), many simulations are done to determine the most sensitive parameter of the proportional-integral (PI) controllers implemented. The most sensitive parameter is selected by evaluating the influence of the proportional gain (Kp) and the integral time (T) in the general performance of the plant when they are changed into the proposed ranges. From the simulation study, Ti is selected as the most sensitive parameter. A comparison between the results in terms of EQI vs OCI graphics, varying Kp and Ti and the results varying only Ti, shows similar behaviours on the plant performance for all strategies.
Keywords :
PI control; wastewater treatment; PI control; control strategies; controllers parameters variation; effluent quality index; general plant performance indicators; integral time; operating cost index graphics; proportional gain; proportional-integral controllers; wastewater treatment plants performance; Aerodynamics; Biological system modeling; Inductors; Rain; Sensitivity; Storms; Tuning;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Emerging Technologies & Factory Automation (ETFA), 2011 IEEE 16th Conference on
Conference_Location :
Toulouse
ISSN :
1946-0740
Print_ISBN :
978-1-4577-0017-0
Electronic_ISBN :
1946-0740
Type :
conf
DOI :
10.1109/ETFA.2011.6059057
Filename :
6059057
Link To Document :
بازگشت