• DocumentCode
    2024306
  • Title

    Method and measurement set up for the evaluation of the performance of UPS in presence of network outages

  • Author

    Pasini, Gaetano ; Peretto, Lorenzo ; Ariatta, Alberto

  • Author_Institution
    Dept. of Electr. Eng., Alma Mater Studiorum - Univ. of Bologna, Bologna, Italy
  • fYear
    2012
  • fDate
    26-28 Sept. 2012
  • Firstpage
    1
  • Lastpage
    5
  • Abstract
    Uninterruptible Power Supply (UPS) are systems capable of providing power supply at the occurrence of voltage dips, swells or power interruptions. In the present paper authors present a new limit curve for assessing the response time of the UPS at the occurrence of high or short impedance service interruption of the UPS feeder. The response time from passing from external power supply to battery operation mode must fulfill requirements reported in Standards or in Councils specifications. The response time is one of the most important features of a UPS. Customers are requiring response times more and more short. This hot topic has lead authors to investigate on a new limit curve for the response time of UPS more severe than conventional ones. Experimental results confirm that actual practicability of such a cure for comparison purposes during tenders.
  • Keywords
    equipment evaluation; power system reliability; testing; uninterruptible power supplies; UPS feeder; high impedance service interruption; network outage; short impedance service interruption; uninterruptable power supply; Batteries; Impedance; Power supplies; Switches; Time factors; Uninterruptible power systems; Voltage measurement; UPS; distributed generation; power quality; response time;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Applied Measurements for Power Systems (AMPS), 2012 IEEE International Workshop on
  • Conference_Location
    Aachen
  • Print_ISBN
    978-1-4673-1540-1
  • Type

    conf

  • DOI
    10.1109/AMPS.2012.6344012
  • Filename
    6344012