• DocumentCode
    2030410
  • Title

    Protection at the speed of light: Arc-flash protection combining arc flash sensing and arc-resistant technologies

  • Author

    Kay, John A. ; Arvola, Juha ; Kumpulainen, Lauri

  • Author_Institution
    Rockwell Autom. Canada, Cambridge, ON, Canada
  • fYear
    2009
  • fDate
    14-16 Sept. 2009
  • Firstpage
    1
  • Lastpage
    7
  • Abstract
    One of the most critical aspects of reducing both personnel injury and equipment damage is through the reduction of the energy available to an arcing fault. The initiation of a trip and the clearing time (opening) of any upstream device is a critical component in the reduction of the resultant arc flash incident energy. Combining technologies that detect and interrogate both arc flash and the associated arc current signatures in combination with arc resistant switchgear or controlgear, can provide a coordinated solution for controlling the level of incident energy at various points within the distribution network. Hybrid systems of this type provide the highest level of personnel protection, along with comprehensive equipment protection, as detection and initiation of tripping is implemented faster than with conventional relaying techniques alone. The reduction of the overall trip time can reduce equipment collateral damage, reconditioning time and lost productivity resulting from downtime. These types of coordinated systems will also lower the personal protective equipment (PPE) requirements based on incident energy. This paper compares several systems including conventional overcurrent protection, zone selective and various light and current sensing systems.
  • Keywords
    arcs (electric); electrical faults; overcurrent protection; switchgear; arc current signatures; arc flash incident energy; arc flash sensing; arc resistant switchgear; arc-flash protection; arc-resistant technologies; arcing fault; distribution network; equipment collateral damage; equipment protection; incident energy level; overcurrent protection; personal protective equipment requirements; personnel protection; Fault currents; Fault detection; Immune system; Optical control; Optical losses; Optical sensors; Personnel; Plasma temperature; Protection; Switchgear; arc faults; arc flash; arc resistant equipment; arc sensors; controlgear; optical arc detection; switchgear;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Petroleum and Chemical Industry Conference, 2009. PCIC 2009. 2009 Record of Conference Papers - Industry Applications Society 56th Annual
  • Conference_Location
    Anaheim, CA
  • ISSN
    0090-3507
  • Print_ISBN
    978-1-4244-3798-6
  • Electronic_ISBN
    0090-3507
  • Type

    conf

  • DOI
    10.1109/PCICON.2009.5297148
  • Filename
    5297148