DocumentCode
2031319
Title
Protection of High-Voltage AC Cables
Author
Tziouvaras, Demetrios A.
Author_Institution
Schweitzer Eng. Lab. Inc.
fYear
0
fDate
0-0 0
Firstpage
48
Lastpage
61
Abstract
High-voltage underground AC cables have significantly different electrical characteristics than overhead transmission lines. The cable sheath or shield grounding method has a major impact on the zero-sequence impedance of underground cables. Understanding how the underground cable grounding method affects the series sequence impedances is very fundamental to underground cable protection. In the paper we briefly discuss the types of underground cables, their bonding and grounding methods, and the fundamental differences between overhead transmission lines and cable electrical characteristics. Finally we discuss the application of short-circuit protection for high-voltage AC cables
Keywords
cable sheathing; cable shielding; earthing; electric impedance; power overhead lines; power transmission protection; short-circuit currents; underground cables; cable bonding; cable electrical characteristic; cable sheath; cable shield grounding method; high-voltage underground cable protection; overhead transmission lines; series sequence impedance; short-circuit protection; zero-sequence impedance; Cable insulation; Circuit faults; Communication cables; Electric variables; Grounding; Impedance; Power transmission lines; Protection; Steel; Underground power cables;
fLanguage
English
Publisher
ieee
Conference_Titel
Protective Relay Engineers, 2006. 59th Annual Conference for
Conference_Location
College Station, TX
Print_ISBN
1-4244-0043-0
Type
conf
DOI
10.1109/CPRE.2006.1638691
Filename
1638691