DocumentCode :
2031699
Title :
Standard CT accuracy ratings in metal-clad switchgear
Author :
Zocholl, S.E.
Author_Institution :
Schweitzer Eng. Lab. Inc., USA
fYear :
2006
fDate :
4-6 April 2006
Abstract :
This paper shows the consequences of low accuracy ratings and analyzes the relay response for fault currents in the range of 25 kA to 50 kA, using the CT accuracy rating from the relay data acquisition. To ensure proper relaying performance, the user should make a careful analysis of CT performance considering the relaying requirements for the specific short circuit current and the secondary circuit impedances. The careful analysis of CT performance for high magnitude offset fault requires computer simulation of the relay, as well as the CT, and cannot be carried out by manual calculation.
Keywords :
current transformers; data acquisition; digital simulation; relay protection; short-circuit currents; switchgear; CT accuracy; computer simulation; data acquisition; fault current; metal-clad switchgear; relaying performance; secondary circuit impedance; short circuit current; Circuit faults; Current measurement; Current transformers; Data acquisition; Digital filters; Digital relays; Fault currents; Protection; Protective relaying; Switchgear;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Protective Relay Engineers, 2006. 59th Annual Conference for
Print_ISBN :
1-4244-0043-0
Type :
conf
DOI :
10.1109/CPRE.2006.1638702
Filename :
1638702
Link To Document :
بازگشت