DocumentCode
2036111
Title
Influence of stator winding structure on the relation between PD value and maximum discharge quantity in deterioration diagnosis of hydro-generators
Author
Hattori, Osamu ; Yamashita, Takahiko
Author_Institution
Grad. Sch. of Sci. & Technol., Nagasaki Univ., Nagasaki, Japan
fYear
2010
fDate
21-24 Nov. 2010
Firstpage
1806
Lastpage
1811
Abstract
In this study, the authors investigated on-line deterioration diagnosis of hydro-generators. Simultaneous measurement was done under off-line condition by using an on-line PD monitor and an off-line PD measuring system. When a stator had wave-winding structure, a good correlation between the maximum electric discharges of the offline PD measuring system and PD values of the online PD monitor was seen. On the other hand, when the stator had lap-winding structure, the correlation was not clear. PD values were small due to weak capacitive coupling of lap-winding structure. Then, PD measurement of hydro-generators with wave-winding structure was done under on-line and off-line conditions by using the PD monitor. Online PD values were slightly higher than offline PD values. From the results mentioned above, on-line PD monitoring is considered to be useful for diagnosis of hydro-generators with wave-winding structure.
Keywords
fault diagnosis; hydroelectric generators; partial discharge measurement; PD value; deterioration diagnosis; electric discharges; hydrogenerators; lap-winding structure; maximum discharge quantity; offline PD measuring system; online PD monitor; online deterioration diagnosis; stator winding structure; wave-winding structure; PD value; deterioration diagnosis; hydro-generator; lap-winding; off-line; on-line; partial discharge; stator winding; wave-winding;
fLanguage
English
Publisher
ieee
Conference_Titel
TENCON 2010 - 2010 IEEE Region 10 Conference
Conference_Location
Fukuoka
ISSN
pending
Print_ISBN
978-1-4244-6889-8
Type
conf
DOI
10.1109/TENCON.2010.5685951
Filename
5685951
Link To Document