Abstract
While the gassing of oil, as determined by periodic dissolved gas analysis (DGA), is attributed to an incipient electrical failure, for the gradual deterioration of paper insulation its aging process is considered to be responsible. These deficiencies, both of which negatively affect the service reliability of high voltage power transformers, are currently perceived as two independent phenomena. In reality, studies indicate that they are interrelated. New laboratory techniques developed for improved monitoring of oil decay, show that gassing has hidden side effects. The outcome of random secondary chemical reactions that follow the decomposition of hydrocarbon chains, also suggest that gassing might be a self-sustained process. This paper describes the relationship between the purity of oil and its stability under electrical stress, as well as the means necessary for maintaining the liquid insulation in pristine condition throughout the entire lifetime of a power transformer.
Keywords
ageing; insulation testing; paper; power transformer insulation; power transformer testing; transformer oil; aging process; electrical stress; high voltage power transformers; laboratory techniques; oil decay monitoring; oil gassing; paper insulation deterioration; periodic dissolved gas analysis; random secondary chemical reactions; self-sustained process; service reliability; stability; Aging; Dielectrics and electrical insulation; Dissolved gas analysis; Gas insulation; Laboratories; Monitoring; Oil insulation; Petroleum; Power transformer insulation; Power transformers;
fLanguage
English
Publisher
ieee
Conference_Titel
Dielectric Liquids, 2002. ICDL 2002. Proceedings of 2002 IEEE 14th International Conference on
Print_ISBN
0-7803-7350-2
Type
conf
DOI
10.1109/ICDL.2002.1022746
Filename
1022746
Link To Document