Optimizing the operation of current differential protection by power differential relay for three phase transformer
Author
Bahmani, B. ; Jahromi, M. Esmi ; Ranjbar, A.M.
Author_Institution
Fars Regional Electr. Co., Shiraz, Iran
fYear
2006
fDate
20-22 March 2006
Firstpage
1
Lastpage
6
Abstract
To avoid the needless trip by magnetizing inrush current, the second harmonic component is commonly used for blocking differential relay in power transformers. However, the main problems of the current comparison method are in the very high inrush currents and relatively small fault currents regarding winding short circuits. Also The second harmonic component in fault current is increased in long lines which may blocks the relay operation. This paper describes a method to discriminate internal fault from inrush current and faults with a high second harmonic component by the sum of active power flowing into the transformer from each terminal. The average power is almost negligible for energizing, but an internal fault consumes large amounts of power.
Keywords
load flow; magnetisation; optimisation; power transformer protection; relay protection; short-circuit currents; transformer windings; active power flow; current differential protection; fault current; inrush current; optimisation; power differential relay; power transformer; second harmonic component; three phase transformer; winding short circuit; Circuit faults; Harmonic analysis; Power transformers; Relays; Surge protection; Surges; Windings; Active Power Relays; EMTP; Magnetizing Inrush; Protection; TACS; Transformer;
fLanguage
English
Publisher
ieee
Conference_Titel
GCC Conference (GCC), 2006 IEEE
Conference_Location
Manama
Print_ISBN
978-0-7803-9590-9
Electronic_ISBN
978-0-7803-9591-6
Type
conf
DOI
10.1109/IEEEGCC.2006.5686196
Filename
5686196
Link To Document