DocumentCode :
2042766
Title :
Voltage control challenges on weak grids with high penetration of wind generation: ERCOT experience
Author :
Shun-Hsien Huang ; Schmall, J. ; Conto, J. ; Adams, J. ; Yang Zhang ; Carter, C.
Author_Institution :
Electr. Reliability Council of Texas (ERCOT Inc.), Taylor, TX, USA
fYear :
2012
fDate :
22-26 July 2012
Firstpage :
1
Lastpage :
7
Abstract :
More than 9 GW of wind capacity has been connected to the Electric Reliability Council of Texas (ERCOT) grid. In order to accommodate the installation of future wind generation, the Competitive Renewable Energy Zone (CREZ) transmission expansion project has been planned. The CREZ project includes over two thousand miles of new 345kV transmission lines and is expected to be completed by 2014. Planning studies have been conducted to ensure that new wind generation can be reliably delivered to the ERCOT grid through the CREZ transmission facilities. Voltage oscillations and temporary overvoltage were observed in the CREZ system dynamic studies. Weak grid as indicated by low Short Circuit Ratio (SCR) was considered to be the primary cause for those voltage issues. This paper presents the analysis, including causes and solutions, for these voltage stability issues. An actual oscillatory response of an existing wind power plant (WPP) captured on a Phasor Measurement Unit (PMU) and its postevent analysis supported all the findings in the CREZ planning studies. Both the real time operation events and planning studies demonstrate the voltage stability impacts of high penetration of wind generation on weak grids.
Keywords :
phase measurement; power generation control; power generation planning; power grids; power system stability; power transmission lines; voltage control; wind power plants; CREZ system dynamic study; CREZ transmission expansion project; ERCOT grid experience; Electric Reliability Council of Texas grid; PMU; SCR; WPP; competitive renewable energy zone; high wind generation penetration; low short circuit ratio; oscillatory response; phasor measurement unit; post event analysis; temporary overvoltage; transmission lines; voltage 345 kV; voltage control; voltage oscillations; voltage stability; weak grids; wind capacity; wind generation penetration; wind power plant; Oscillators; Phasor measurement units; Planning; Power system stability; Stability analysis; Thyristors; Voltage control; Low Short Circuit Ratio; Phasor Measurement Unit (PMU); Temporary Overvoltage; Voltage Oscillations; Weak Grid; Wind Generation;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Power and Energy Society General Meeting, 2012 IEEE
Conference_Location :
San Diego, CA
ISSN :
1944-9925
Print_ISBN :
978-1-4673-2727-5
Electronic_ISBN :
1944-9925
Type :
conf
DOI :
10.1109/PESGM.2012.6344713
Filename :
6344713
Link To Document :
بازگشت