DocumentCode
2045573
Title
Analysis of armature winding internal faults and design of main protection scheme for synchronous generators
Author
Shanming, Wang ; Lin, Gui ; Xiangheng, Wang ; Yuguang, Sun ; Weijian, Wang ; Jianping, Wang
Author_Institution
Tsinghua Univ., Beijing, China
Volume
1
fYear
2004
fDate
5-8 April 2004
Firstpage
148
Abstract
To analyze the internal faults, the multi loop model of synchronous generators, based on the multi loop method, is introduced in this paper. Using this model, the main protection configuration schemes for two 135 MW generators and two 700 MW three gorges generators with different stator winding arrangements are analyzed in detail. These design examples reveal that the main protection configuration scheme must be based on the analysis and simulation of possible slot and end faults.
Keywords
electrical faults; machine protection; machine windings; stators; synchronous generators; 135 MW; 700 MW; armature winding internal faults; end faults; multi loop model; protection scheme; slot faults; stator winding arrangements; synchronous generator; three gorges generators;
fLanguage
English
Publisher
iet
Conference_Titel
Developments in Power System Protection, 2004. Eighth IEE International Conference on
ISSN
0537-9989
Print_ISBN
0-86341-385-4
Type
conf
DOI
10.1049/cp:20040085
Filename
1364828
Link To Document