Title :
Failure of polyester spacer at low voltage equipment
Author :
Moradian, A.R. ; Mohseni, M. ; Estifa, F.
Author_Institution :
Dept. of High Voltage, Niroo Res. Inst., Tehran, Iran
Abstract :
Arak Refinery plant of Iran confronted a number of failures of low voltage equipment. Our investigations after each event have shown that the phases of vertical busbars are connected together electrically and this caused flashover between them. Also, vertical busbars melted near the surface of spacers. Our inspections showed that degradation of polyester spacers left carbon on their surface and increased the surface conductivity between phases and neutral. So using general-purpose polyester in low voltage equipment at 50°C for long duration or higher temperature will cause surface conductivity
Keywords :
busbars; flashover; organic insulating materials; surface conductivity; 50 C; busbar melting; failure; flashover; low voltage equipment; polyester spacer; spacer degradation; spacer surface; surface conductivity; vertical busbars; Conductivity; Degradation; Dielectrics and electrical insulation; Inspection; Low voltage; Materials testing; Resins; Shape; Switches; Temperature;
Conference_Titel :
Electrical Insulation, 2000. Conference Record of the 2000 IEEE International Symposium on
Conference_Location :
Anaheim, CA
Print_ISBN :
0-7803-5931-3
DOI :
10.1109/ELINSL.2000.845516