DocumentCode :
2046048
Title :
Effects of fault arcs on insulating walls in electrical switchgear
Author :
Finke, Wirtsch S. ; Koenig, D. ; Kaltenborn, U.
Author_Institution :
High Voltage Lab., Tech. Hochschule Darmstadt, Germany
fYear :
2000
fDate :
2000
Firstpage :
386
Lastpage :
389
Abstract :
This paper deals with test methods to evaluate the effects of high current fault arcs occurring in electrical switchgear compartments stressing insulating walls made of different materials. These partitions are stressed mechanically and thermally. To study these effects several test arrangements were developed and relevant experimental studies performed. The performance of the investigated materials is presented and discussed
Keywords :
arcs (electric); epoxy insulation; fault currents; insulation testing; plastics; switchgear insulation; compression phase; electrical switchgear; emission phase; expansion phase; fire resistance; high current fault arcs; insulating walls; mechanically stressed partitions; plastics use; test facilities; thermally stressed partitions; Arc discharges; Dielectrics and electrical insulation; Gas insulation; IEC standards; Laboratories; Low voltage; Medium voltage; Plasma temperature; Switchgear; Testing;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Electrical Insulation, 2000. Conference Record of the 2000 IEEE International Symposium on
Conference_Location :
Anaheim, CA
ISSN :
1089-084X
Print_ISBN :
0-7803-5931-3
Type :
conf
DOI :
10.1109/ELINSL.2000.845531