DocumentCode
2046344
Title
Streamer propagation in composite oil/cellulose insulation under LI voltages
Author
Liu, Rongsheng ; Jaksts, Albert ; Bengtsson, Tord
Author_Institution
ABB Corp. Res., Vasteras, Sweden
fYear
2000
fDate
2000
Firstpage
426
Lastpage
430
Abstract
A needle/plane geometry was used to study fundamental properties of streamer propagation in composite transformer oil/cellulose insulation under LI (lightning impulse: 1.2/50 μs) voltages. The plane electrode was either an aluminium plate (bare oil gap) or covered with laminated oil-impregnated paper of different thickness. Breakdown voltage and streamer propagation speed were seen to differ at different polarities and dependent on the gap length of the needle/plane geometry. A ratio of oil-gap length to electrode cover thickness seems to exist, below which, the cover thickness dominates the breakdown of the composite insulation. Above that, length of the oil gap dominates the breakdown
Keywords
discharges (electric); electric breakdown; impregnated insulation; paper; transformer oil; Al; aluminium plate; breakdown voltage; composite transformer oil/cellulose insulation; laminated oil impregnated paper; lightning impulse voltage; needle-plane electrode system; oil gap; streamer propagation; Aluminum; Electric breakdown; Electrodes; Geometry; Lightning; Needles; Oil insulation; Optical propagation; Petroleum; Power transformer insulation;
fLanguage
English
Publisher
ieee
Conference_Titel
Electrical Insulation, 2000. Conference Record of the 2000 IEEE International Symposium on
Conference_Location
Anaheim, CA
ISSN
1089-084X
Print_ISBN
0-7803-5931-3
Type
conf
DOI
10.1109/ELINSL.2000.845540