    138 kV phase shifting transformer protection: EMTP modeling and model power system testing

  • Author

    Tziouvaras, D.A. ; Jimenez, R.

  • Author_Institution
    Schweitzer Eng. Labs., ComEd, USA
  • Volume
    1
  • fYear
    2004
  • fDate
    5-8 April 2004
  • Firstpage
    343
  • Abstract
    This paper describes the protection of a 138 kV, 300 MVA phase shifting transformer (PST), and the issues associated with differential protection stability during external faults that cause PST series winding saturation. In addition, this paper discusses PST modeling using the electromagnetic transients program (EMTP). EMTP modeling is necessary to verify the protective relaying settings for the particular application and their applicability to different fault scenarios and operating conditions. For the case study detailed in this paper, we verified the relay settings by playing the EMTP transient data back into the protective relays using an open loop approach. From the test data, we made setting changes and other enhancements that increased the PST protection system security for external faults.
  • Keywords
    EMTP; phase shifters; power system faults; power transformer protection; relay protection; transformer windings; 138 kV; 300 MVA; EMTP modeling; PST; differential protection stability; digital relay; external faults; model power system testing; open loop method; phase shifting transformer; phase-angle regulator; protective relaying settings; series winding saturation; transformer protection;
  • fLanguage
    English
  • Publisher
    iet
  • Conference_Titel
    Developments in Power System Protection, 2004. Eighth IEE International Conference on
  • ISSN
    0537-9989
  • Print_ISBN
    0-86341-385-4
  • Type

    conf

  • DOI
    10.1049/cp:20040133
  • Filename
    1364876