Title :
A transformer differential relay with a core saturation detection algorithm
Author :
Kang, Y.C. ; Won, S.H. ; Kang, S.H. ; Crossley, P.A.
Author_Institution :
NPTC, Chonbuk Nat. Univ., Chonju, South Korea
Abstract :
The differential current for transformer protection has points of inflection at the start and end of each saturation period of the core during magnetic inrush and over-excitation. These points can be detected using the third-difference function of the differential current. This paper proposes a current differential relay for transformer protection that operates in conjunction with a core saturation detection algorithm. If the magnitude of the third-difference function exceeds the threshold, the blocking signal is issued and maintained for one cycle. A method is designed to discriminate between transformer saturation and current transformer (CT) saturation. The performance of the proposed blocking scheme was compared with a conventional harmonic blocking scheme. Test results indicate that the proposed scheme can discriminate between magnetic inrush and internal faults and reduce the delay of the operating time of a relay for an internal fault when a CT saturates.
Keywords :
current transformers; fault currents; power transformer protection; relay protection; transformer cores; core over-excitation; core saturation detection algorithm; core saturation period; current transformer saturation; differential current; inflection points; internal faults; magnetic inrush current; power transformer differential protection; relay protection; third difference function;
Conference_Titel :
Developments in Power System Protection, 2004. Eighth IEE International Conference on
Print_ISBN :
0-86341-385-4
DOI :
10.1049/cp:20040139