New algorithm for low-impedance restricted earth fault protection
Author
Kasztenny, B. ; Sevov, L. ; Jaques, A.
Author_Institution
Gen. Electr. Multilin, Canada
Volume
1
fYear
2004
fDate
5-8 April 2004
Firstpage
372
Abstract
A new algorithm for low-impedance restricted earth fault (REF) protection is presented in this paper. The algorithm uses a unique definition of the restraining current for enhanced sensitivity and security on current transformer (CT) saturation. While ensuring good sensitivity and excellent security, the trip time of the actual relay hardware implementing the presented algorithm is below one power cycle. The described algorithm is a standard function on commercially available transformer and generator numerical relays with more than one thousand unit-years of combined field experience to date.
Keywords
current transformers; earthing; fault currents; power transformer protection; relay protection; CT saturation security; CT saturation sensitivity; current transformer; low-impedance restricted earth fault protection; numerical relays; relay protection; relay trip time; restraining current;