DocumentCode
2046775
Title
The research of the sampling method for CT saturation for numerical busbar protection
Author
Li-Jun, Cheng
Author_Institution
Nanjing Autom. Res. Inst., China
Volume
1
fYear
2004
fDate
5-8 April 2004
Firstpage
384
Abstract
The busbar protection is the most important relays in plants and substations of power system. It has direct effect on the security and stability for an electric power system. The busbar protection has thus a maximum degree of security against spurious operation for external short-circuits. At the same time, it ensures that in the event of internal short-circuits a tripping signal is initiated within the very short time of less than a half-cycle. The main features for modem busbar protection are rapid speed and sensitive trip for internal faults (tripping time less than 10 ms), stability for external faults, especially during current transformer (CT) saturation. So the protection algorithm must provide simplicity, rapid computation and identification. Considering the busbar protection principle and CT saturation, the sampling differential current algorithm is the better choice for the numerical busbar protection. The main requirement that a busbar protection scheme has to fulfill is proper behavior in the case of CT saturation. Many projects for CT saturation have successfully been used in busbar protections. For example, the ´mid-impedance principle´ using a very simple design to achieve a rapid, stable and sensitive detection for a fault condition, the ´checking CT saturation unit´ identifying whether the CT saturating or not, are the effective methods. The ´maximum-value holding method´ applied prior to the Fourier filtering is largely insensitive to CT saturation phenomena. The high-impedance busbar protection and the linear couplers can be used to overcome the problems caused by CT saturation, and so on. These methods have been used in the historical or the new products. Two methods, the synchronizing identification and the phase current comparison, are discussed in this paper.
Keywords
busbars; current transformers; power system faults; power system protection; power system security; power system stability; relay protection; transformer protection; CT saturation; current transformers; numerical busbar protection; phase current comparison method; power system security; power system stability; relay protection; sampling differential current algorithm; short-circuit faults; synchronizing identification method;
fLanguage
English
Publisher
iet
Conference_Titel
Developments in Power System Protection, 2004. Eighth IEE International Conference on
ISSN
0537-9989
Print_ISBN
0-86341-385-4
Type
conf
DOI
10.1049/cp:20040143
Filename
1364886