DocumentCode :
2049559
Title :
Applying current limiting fuses with modern molded case circuit breakers
Author :
Fussell, Kenneth J.
Author_Institution :
Parsons Main Inc, Charlotte, NC, USA
fYear :
1994
fDate :
4-5 May 1994
Firstpage :
1
Lastpage :
8
Abstract :
The application of current limiting fuses to reduce short circuit duty is complicated by the current limiting aspects of modern breaker design. The problem of applying current limiting fuses in conjunction with modern design breakers is explored in a new installation. This installation is a 3000 kVA unit substation in a cogeneration facility. This paper analyzes a problem encountered in a design where modern breakers were installed downstream of current limiting fuses and extrapolates the findings to other applications
Keywords :
circuit breakers; cogeneration; electric fuses; limiters; substations; 3000 kVA; cogeneration facility; current limiting fuses; molded case circuit breakers; short circuit duty reduction; substation; Circuit breakers; Circuit faults; Cogeneration; Computer aided software engineering; Current limiters; Fuses; Modems; Substations; Switchgear; Visualization;