• DocumentCode
    2056029
  • Title

    An investigation into the operation life of transformers

  • Author

    Xin Wang ; Xin Zhang

  • Author_Institution
    Gansu Electr. Power Res. Inst., Lanzhou, China
  • fYear
    2012
  • fDate
    10-14 Sept. 2012
  • Firstpage
    1
  • Lastpage
    4
  • Abstract
    This paper presents results of a study on solid insulation aging of a number of oil-immersed power transformers, some of them have operated for more than 40 years. The contents of furfurol were measured, in addition to that of dissolved gases in transformer oil, by applying the HPLC method. Based on measured data and the traditional theory of solid insulation aging, it is suggested that the aging of solid insulation in these transformers is not serious even after 50 years´ of continued operation, because there has been no local overheating or sustained transformer overload during their operation.
  • Keywords
    ageing; power transformer insulation; transformer oil; HPLC method; oil-immersed power transformers; solid insulation aging theory; sustained transformer overload; transformer operation life; Content of furfurol; insulation aging; solid insulation;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Electricity Distribution (CICED), 2012 China International Conference on
  • Conference_Location
    Shanghai
  • ISSN
    2161-7481
  • Print_ISBN
    978-1-4673-6065-4
  • Electronic_ISBN
    2161-7481
  • Type

    conf

  • DOI
    10.1109/CICED.2012.6508406
  • Filename
    6508406