An investigation into the operation life of transformers
Author
Xin Wang ; Xin Zhang
Author_Institution
Gansu Electr. Power Res. Inst., Lanzhou, China
fYear
2012
fDate
10-14 Sept. 2012
Firstpage
1
Lastpage
4
Abstract
This paper presents results of a study on solid insulation aging of a number of oil-immersed power transformers, some of them have operated for more than 40 years. The contents of furfurol were measured, in addition to that of dissolved gases in transformer oil, by applying the HPLC method. Based on measured data and the traditional theory of solid insulation aging, it is suggested that the aging of solid insulation in these transformers is not serious even after 50 years´ of continued operation, because there has been no local overheating or sustained transformer overload during their operation.
Keywords
ageing; power transformer insulation; transformer oil; HPLC method; oil-immersed power transformers; solid insulation aging theory; sustained transformer overload; transformer operation life; Content of furfurol; insulation aging; solid insulation;