DocumentCode :
2056232
Title :
Fault reason analysis of 10kV cable lines of city power grid with OWTS state detection
Author :
Zuo-chun Zhou ; Yanyan Zhang ; Huachun Li
Author_Institution :
BEPRI, China
fYear :
2012
fDate :
10-14 Sept. 2012
Firstpage :
1
Lastpage :
8
Abstract :
In order to supply power to Olympic Games in 2008, OWTS(Oscillating Wave Test System) was introduced to Beijing. Many tests proved that OWTS is an effective way to find faults in 10kV cable joints that are newly installed. In 2011 Beijing Electric Power Corporation detected the state of 10kV cable lines sent by Power Supply Company in Beijing with OWTS(oscillating wave test system). We disassemble 10kV cable joints and found that Partial Discharge exceeded. We found many faults in 10kV cable joints, then analyzed 4 major factors that can influence the quality of cable joints in details, and made suggestions for revision.
Keywords :
cables (electric); fault diagnosis; partial discharges; power grids; power supply quality; Beijing electric power corporation; OWTS state detection; cable lines; city power grid; fault reason analysis; oscillating wave test system; partial discharge; voltage 10 kV; OWTS; defect; state detection;