    This paper discusses the distance relay tripping characteristic in the case of installation of Static Synchronous Series Compensator (SSSC) which is categorized as a series connected Flexible Alternating Current Transmission System (FACTS) device and pays especial attention to the over-reaching problem. This is done by presenting the measured impedance at the relaying point in the case of SSSC presence at the near end of the next line. Distance relay tripping characteristic is greatly influenced in the presence of SSSC on the transmission line or even in the case of installation of SSSC on the near end of the next line. Distance relay tripping characteristic depends on many factors including the power system structural conditions, the pre-fault loading, the ground fault resistance, SSSC controlling parameters, and the coupling transformer impedance.
  • Keywords
    Control systems; Couplings; Flexible AC transmission systems; Impedance measurement; Power system faults; Power system relaying; Power transmission lines; Protective relaying; Relays; Transmission line measurements;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Power Engineering, Energy and Electrical Drives, 2007. POWERENG 2007. International Conference on
  • Conference_Location
    Setubal, Portugal
  • Print_ISBN
    978-1-4244-0895-5
  • Electronic_ISBN
    978-1-4244-0895-5
  • Type

    conf

  • DOI
    10.1109/POWERENG.2007.4380148
  • Filename
    4380148