DocumentCode
2056898
Title
FEM simulation of temperature field of dry-type transformer
Author
Chunhua Li ; Baoguo Su ; Guangyu Zhou
Author_Institution
Shandong Luneng Mount.Tai Electr. Equip. Co., Ltd., China
fYear
2012
fDate
10-14 Sept. 2012
Firstpage
1
Lastpage
4
Abstract
In order to calculate winding temperature of dry-type transformer in accurate way, it is necessary to base on the theory of heat transfer and the theory of hydrodynamics and carry out simulation computation on winding temperature distribution of dry-type transformer by means of FLUENT software. We take the winding temperature of 3 dry-type transformers with different capacity as an illustration. Through comparison between High and low voltage winding temperature, the calculation and test results show that all errors range from -4K to 0K. This calculation method can accurately compute winding temperature and its distribution location and provide the basis for design, research and development and operational maintenance of similar products.
Keywords
finite element analysis; maintenance engineering; power engineering computing; power transformers; transformer windings; FEM simulation; FLUENT software; carry out simulation computation; distribution location; dry-type transformer; heat transfer theory; hydrodynamics; operational maintenance; research and development; temperature -4 K to 0 K; temperature field; winding temperature distribution; FLUENT; dry-type transformer; temperature field; winding;
fLanguage
English
Publisher
ieee
Conference_Titel
Electricity Distribution (CICED), 2012 China International Conference on
Conference_Location
Shanghai
ISSN
2161-7481
Print_ISBN
978-1-4673-6065-4
Electronic_ISBN
2161-7481
Type
conf
DOI
10.1109/CICED.2012.6508441
Filename
6508441
Link To Document