  • Abstract
    In this report, the EdF´s test for the high temperature vulcanized (HTV) silicone rubber insulator was performed up to 2000 hours. Evaluation of the aging sample was performed from measured results such as chemical analysis, hardness and surface roughness during the test. The acceleration factor of a salt-fog test was estimated from alumina trihydrate (ATH) reduction rate on the chemical analysis by comparing with EdF´s test results. It was found that the acceleration factor of the salt-fog test under a certain conditions was about 90, which was 6 times higher than that of EdF´s test
  • Keywords
    ageing; chemical analysis; hardness; insulator testing; rough surfaces; silicone rubber insulators; 2000 hour; EDF; acceleration factor; aging polymer insulator testing; alumina trihydrate reduction rate; chemical analysis; hardness; high temperature vulcanized silicone rubber insulator; insulator breakdown tests; salt-fog test; surface roughness; Aging; Chemical analysis; Insulator testing; Life estimation; Performance evaluation; Plastic insulation; Polymers; Rough surfaces; Rubber; Temperature;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Electrical Insulating Materials, 2001. (ISEIM 2001). Proceedings of 2001 International Symposium on
  • Conference_Location
    Himeji
  • Print_ISBN
    4-88686-053-2
  • Type

    conf

  • DOI
    10.1109/ISEIM.2001.973670
  • Filename
    973670