Abstract :
This paper presents the design of a cable connector used in partial discharge and dielectric loss tests. The body of the connector is constructed using an acrylic tube and PVC, and oil is used as an insulating medium. In order to implement the connector, partial discharges and the dielectric loss (tan δ) of a cable are tested according to IEC standards. It is found that the cable connector proposed can give satisfactory and reasonably accurate results from the measurements. In addition, the cost of the construction of the connector developed is cheaper than that of the commercial module
Keywords :
IEC standards; XLPE insulation; dielectric loss measurement; electric connectors; insulating oils; insulation testing; partial discharge measurement; power cable insulation; underground cables; 12 kV; 21 kV; IEC standards; PVC; Schering bridge; XLPE cable; acrylic tube; air insulation; cable connector; cable terminator; cable testing; connector construction cost; dielectric loss measurements; insulating oil; palm oil; partial discharge measurements; underground cable; Connectors; Costs; Dielectric losses; Dielectric measurements; Dielectrics and electrical insulation; IEC standards; Oil insulation; Partial discharges; Petroleum; Testing;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Electrical Insulating Materials, 2001. (ISEIM 2001). Proceedings of 2001 International Symposium on
Conference_Location :
Himeji
Print_ISBN :
4-88686-053-2
Type :
conf
DOI :
10.1109/ISEIM.2001.973719
Filename :
973719
Link To Document :
بازگشت