• DocumentCode
    2059298
  • Title

    Study and application of switching operation of 10kV lines ring network in urban power distribution network

  • Author

    Xueli Guo ; Jiuju Du ; Changxiao Qi

  • Author_Institution
    Nanyang Power Co., Nanyang, China
  • fYear
    2012
  • fDate
    10-14 Sept. 2012
  • Firstpage
    1
  • Lastpage
    6
  • Abstract
    Switching operation of 10kV line´s ring network is one of the effective technical measures to reduce power failure and improve supply reliability of urban power distribution network. The switching operation of ring network in urban power distribution network is not only affected by operation mode of power system and structure of distribution network, but also restrained by factors such as load and voltage difference prior to closing loop operation, and the overlarge circulating power load during closing loop operation can endanger the safety of power distribution network and equipments. Based on the complicated structure of power distribution network with multiple segments and connections in Nanyang city, the mathematic model of switching operation of ring network in power distribution network is established, which conducts load flow calculation and analysis of closing loop operation with the integrated analysis system of power system for 10kV circuits of different 220kV systems and under different operation modes. This is to protect the setting value and dynamic stability limitation checking of the equipment. Through practicing, method of reducing power flow of closing loop can be proposed and the management system of urban distribution ring network operation standard can be established.
  • Keywords
    load flow; power distribution faults; power distribution reliability; power system management; Nanyang city; closing loop operation; dynamic stability limitation checking; integrated analysis system; load flow calculation; management system; mathematic model; operation mode; overlarge circulating power load; power failure; power flow; power system; ring network; setting value; supply reliability; switching operation; urban power distribution network; voltage 10 kV; voltage 220 kV; voltage difference; closing loop operation; load flow; power supply reliability; switching operation of ring network; urban power distribution network;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Electricity Distribution (CICED), 2012 China International Conference on
  • Conference_Location
    Shanghai
  • ISSN
    2161-7481
  • Print_ISBN
    978-1-4673-6065-4
  • Electronic_ISBN
    2161-7481
  • Type

    conf

  • DOI
    10.1109/CICED.2012.6508537
  • Filename
    6508537