• DocumentCode
    20598
  • Title

    Investigation on the Arc Phenomenon of Air DC Circuit Breaker

  • Author

    Hao Sun ; Mingzhe Rong ; Zhexin Chen ; Chao Hou ; Yushu Sun

  • Author_Institution
    State Key Lab. of Electr. Insulation & Power Equip., Xi´an Jiaotong Univ., Xi´an, China
  • Volume
    42
  • Issue
    10
  • fYear
    2014
  • fDate
    Oct. 2014
  • Firstpage
    2706
  • Lastpage
    2707
  • Abstract
    Comparison analysis on the arc phenomenon of an air dc circuit breaker both in the resistive and inductive circuit was conducted in this paper. It is an interesting phenomenon that severe restrikes occurred in the resistive circuit. According to the results, the reason is that the arc current falls sharply witbreak the rise of arc voltage in the resistive circuit so that the lack of the Lorentz force and the pressure difference before and behind the arc made the hot gas move back toward the entrance of the arc chamber.
  • Keywords
    arcs (electric); circuit breakers; Lorentz force; air dc circuit breaker; arc chamber; arc current; arc phenomenon; arc voltage; difference; inductive circuit; pressure difference; resistive circuit; Atmospheric modeling; Circuit breakers; Educational institutions; Interrupters; Lorentz covariance; Plasmas; Sun; Arc plasma; DC circuit breaker; DC circuit breaker.; experiment research;
  • fLanguage
    English
  • Journal_Title
    Plasma Science, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0093-3813
  • Type

    jour

  • DOI
    10.1109/TPS.2014.2343257
  • Filename
    6874585