• DocumentCode
    2059866
  • Title

    Study for theory and method of on-line detection of power system transient harmonic

  • Author

    Liao, Ruijin ; Sun, Caixin ; Li, Jian ; Song, Yang ; Ge, Yi

  • Author_Institution
    Key Lab. of High Voltage Eng. & Electr. New Technol., Chongqing Univ., China
  • fYear
    2001
  • fDate
    2001
  • Firstpage
    781
  • Lastpage
    784
  • Abstract
    This paper describes the theory of on-line detection of power system transient harmonic. A new on-line detection method using RMS (root-mean-square) of harmonics amount as trigger is presented for the first time. The passive sensor applying electric-magnetic isolated method and the synchronous sampling circuits used for tracking the changes of power system frequency are studied and designed. The contrasting analysis of the input wave with the reverse synthetic input wave by detecting results in a laboratory verifies the correctness of this method. Finally, the results of transient harmonic detected in the substation are given
  • Keywords
    power system harmonics; power system transients; substations; RMS; electric-magnetic isolated method; input wave; passive sensor; power system frequency; power system transient harmonic detection; reverse synthetic input wave; substation; synchronous sampling circuits; Circuits; Frequency; Laboratories; Power system analysis computing; Power system harmonics; Power system transients; Power systems; Sampling methods; Sensor systems; Substations;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Electrical Insulating Materials, 2001. (ISEIM 2001). Proceedings of 2001 International Symposium on
  • Conference_Location
    Himeji
  • Print_ISBN
    4-88686-053-2
  • Type

    conf

  • DOI
    10.1109/ISEIM.2001.973794
  • Filename
    973794