DocumentCode
2059987
Title
Study on pulse current of typical PD models in power transformer
Author
Wang, Guoli ; Hao, Yanpeng ; Li, Yanming
Author_Institution
Dept. of Electr. Eng., Xi´´an Jiaotong Univ., China
fYear
2001
fDate
2001
Firstpage
797
Lastpage
800
Abstract
In power transformer, partial discharge (PD) detection is an effective means for monitoring and evaluation of dielectric faults in an early stage of development. Traditional PD detection methods cannot completely depict discharge mechanism of insulation system, so pulse current of PD should be investigated. In this paper, a broad band measuring system is developed and the high speed digital oscilloscope TDS680B is used to measure pulse current of PD. The whole setup is tested by the PD pulse of standard corona model. Then several typical PD defect models in power transformer are designed and these pulse current are measured by this system. Results show that, the PD pulse in oil is always instability and oscillatory. Moreover, for different models, the parameters of pulse are different, which can be made the reference of PD pattern recognition
Keywords
corona; digital storage oscilloscopes; insulating oils; partial discharge measurement; power transformer insulation; power transformer testing; transformer oil; broad band measuring system; dielectric faults monitoring; discharge mechanism; high speed digital oscilloscope; insulating oil breakdown tests; partial discharge detection; power transformer PD models; pulse current measurement; Current measurement; Dielectric measurements; Fault detection; Monitoring; Partial discharges; Power system modeling; Power transformers; Pulse measurements; Pulse transformers; Velocity measurement;
fLanguage
English
Publisher
ieee
Conference_Titel
Electrical Insulating Materials, 2001. (ISEIM 2001). Proceedings of 2001 International Symposium on
Conference_Location
Himeji
Print_ISBN
4-88686-053-2
Type
conf
DOI
10.1109/ISEIM.2001.973798
Filename
973798
Link To Document