    Fault location of transformer winding deformation using frequency response analysis

  • Author

    Zhijian, Jin ; Minglin, Zhu ; Zishu, Zhu

  • Author_Institution
    Electr. Power Sch., Shanghai Jiao Tong Univ., China
  • fYear
    2001
  • fDate
    2001
  • Firstpage
    841
  • Lastpage
    844
  • Abstract
    FRA (frequency response analysis) is the best effective method that can successfully detect transformer winding deformation. This paper tries to diagnose the fault by the winding´s physical parameter changes. At frequencies lower than critical frequency, the transformer winding may be modeled as a lossless transmission line that the series capacitance could be easily neglected. The parameters of inductance and grounding capacitance may be determined respectively. Any change in these parameters then should reflect the probable position of transformer winding deformation
  • Keywords
    fault location; frequency response; parameter estimation; power transformers; transformer windings; transmission line theory; fault diagnosis; fault location; frequency response analysis; grounding capacitance; inductance; lossless transmission line; parameter estimation; series capacitance; transformer winding deformation detection; Capacitance; Circuit faults; Fault diagnosis; Fault location; Frequency response; Impedance; Inductance; Power transformer insulation; Surges; Windings;