Abstract :
Electromagnetic interferences on control cables may become serious in 500kV gas insulated substation (GIS) of a nuclear plant while the length of the cable increases. The currents on the shield of control cable caused by short circuit and lightning are calculated by means of method of moments (MOM) in the paper. Then the induced voltage across the port of cable is obtained by means of transfer impedance. Based on the calculated results, the influences of different factors, such as the length of control cable, the soil resistivity and the copper strip laid along with the control cable on the interference on control cable are studied. The conclusion in the paper is the foundation for designing of nuclear plant and selecting of electrical equipments.
Keywords :
cable shielding; electrical resistivity; electromagnetic interference; gas insulated substations; method of moments; nuclear power stations; soil; GIS; MOM; cable shielding; control cables; copper strip; electrical equipments; electromagnetic interference analysis; gas insulated substation; lightning; method of moments; nuclear plant; short circuit; soil resistivity; transfer impedance; voltage 500 kV; Cable shielding; Conductivity; Copper; Lightning; Power cables; Soil; Strips; Cable shielding; Electromagnetic interference; Lightning protection; Short circuit currents; Transfer impedance;
Conference_Titel :
Microwave Technology & Computational Electromagnetics (ICMTCE), 2013 IEEE International Conference on
Conference_Location :
Qingdao
DOI :
10.1109/ICMTCE.2013.6812467