• DocumentCode
    2076407
  • Title

    Assessment of insulation condition of 130 kV oil-paper current transformers using return voltage measurements and an expert system

  • Author

    Krivda, A. ; Neimanis, R. ; Gubanski, S.M.

  • Author_Institution
    Vattenfall Utveckling, Stockholm, Sweden
  • Volume
    1
  • fYear
    1997
  • fDate
    19-22, Oct 1997
  • Firstpage
    210
  • Abstract
    An automated pattern recognition system for the assessment of insulation condition of 130 kV oil-paper current transformers has been developed. The system uses polarisation spectra as obtained by return voltage measurements to estimate the state of high voltage (HV) insulation. Preliminary results show that the system is very reliable, decisions are reached within few seconds and the results fully agree with tan δ measurements upon which previous estimates of insulation degradation were based. Moreover, return voltage measurements are easy to apply, offer robust performance in field environment and the equipment is less bulky
  • Keywords
    composite insulating materials; current transformers; diagnostic expert systems; dielectric polarisation; insulation testing; paper; pattern recognition; power transformer insulation; power transformer testing; transformer oil; voltage measurement; 130 kV; automated pattern recognition; expert system; high voltage insulation diagnostics; oil-paper current transformer; polarisation spectra; return voltage measurement; Current transformers; Dielectric measurements; Electric variables measurement; Loss measurement; Oil insulation; Partial discharge measurement; Polarization; Power transformer insulation; Time measurement; Voltage measurement;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Electrical Insulation and Dielectric Phenomena, 1997. IEEE 1997 Annual Report., Conference on
  • Conference_Location
    Minneapolis, MN
  • Print_ISBN
    0-7803-3851-0
  • Type

    conf

  • DOI
    10.1109/CEIDP.1997.634596
  • Filename
    634596