• DocumentCode
    2081256
  • Title

    Some aspects of a digital method for the measurement of loss factor of high voltage insulation

  • Author

    Zhang, Zhengkao ; Raghuveer, M.R.

  • Author_Institution
    Dept. of Electr. & Comput. Eng., Manitoba Univ., Winnipeg, Man., Canada
  • Volume
    1
  • fYear
    1997
  • fDate
    19-22, Oct 1997
  • Firstpage
    279
  • Abstract
    Periodic monitoring of the insulation condition of power system apparatus is necessary in order to estimate its deterioration and maintain the reliability of electric power supply. In this paper a digital technique for the on-line evaluation of loss factor is presented. The Discrete Fourier Transform is applied to the acquired voltage and current signals and the loss factor computed by consideration of the phase shift between the fundamental quantities of voltage and current. The effects of sampling rate, the number of measurements and system frequency fluctuation on the estimated value of loss factor are discussed
  • Keywords
    dielectric loss measurement; discrete Fourier transforms; insulation testing; current signal; digital measurement; discrete Fourier transform; electric power supply; high voltage insulation; loss factor; monitoring; on-line evaluation; phase shift; power system apparatus; reliability; sampling rate; system frequency fluctuation; voltage signal; Condition monitoring; Dielectrics and electrical insulation; Discrete Fourier transforms; Frequency estimation; Loss measurement; Maintenance; Power system measurements; Power system reliability; Umbilical cable; Voltage;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Electrical Insulation and Dielectric Phenomena, 1997. IEEE 1997 Annual Report., Conference on
  • Conference_Location
    Minneapolis, MN
  • Print_ISBN
    0-7803-3851-0
  • Type

    conf

  • DOI
    10.1109/CEIDP.1997.634613
  • Filename
    634613