In this study, experimental investigation has been carried out for the defect detecting capability of two different way of the OW (oscillating wave) voltage test, such as with-cable-charging and without-cable-charging method. For this purpose, two types of OW voltage tests have been performed at the laboratory on the 22.9 kV CN/CV cables in which artificial needle-type and knifecut-type defects were well integrated. Based on the test results, it could be remarked that the with-cable-charging method is more appropriate to the after laying test due to its consistency of the test condition regardless of the cable length under testing
Keywords
cable laying; insulation testing; power cable insulation; power cable testing; power cables; 22.9 kV; CN/CV cable; after-laying test; defect detection; distribution power cable; knifecut-type defects; needle-type defects; oscillating wave voltage test; with-cable-charging; without-cable-charging; Cable insulation; Capacitors; Circuit testing; Frequency; Insulation testing; Insulator testing; Power cables; System testing; Underground power cables; Voltage;
fLanguage
English
Publisher
ieee
Conference_Titel
Electrical Insulation and Dielectric Phenomena, 1997. IEEE 1997 Annual Report., Conference on
Conference_Location
Minneapolis, MN
Print_ISBN
0-7803-3851-0
Type
conf
DOI
10.1109/CEIDP.1997.634626
Filename
634626
Link To Document