• DocumentCode
    2084943
  • Title

    A study on the oscillating wave voltage test as an after-laying test for distribution power cables

  • Author

    Koo, J.U. ; Kim, J.T. ; Lee, J.S. ; Kim, S.J. ; Song, I.K. ; Kim, J.Y. ; Cho, Y.O.

  • Author_Institution
    Hanyang Univ., South Korea
  • Volume
    1
  • fYear
    1997
  • fDate
    19-22, Oct 1997
  • Firstpage
    334
  • Abstract
    In this study, experimental investigation has been carried out for the defect detecting capability of two different way of the OW (oscillating wave) voltage test, such as with-cable-charging and without-cable-charging method. For this purpose, two types of OW voltage tests have been performed at the laboratory on the 22.9 kV CN/CV cables in which artificial needle-type and knifecut-type defects were well integrated. Based on the test results, it could be remarked that the with-cable-charging method is more appropriate to the after laying test due to its consistency of the test condition regardless of the cable length under testing
  • Keywords
    cable laying; insulation testing; power cable insulation; power cable testing; power cables; 22.9 kV; CN/CV cable; after-laying test; defect detection; distribution power cable; knifecut-type defects; needle-type defects; oscillating wave voltage test; with-cable-charging; without-cable-charging; Cable insulation; Capacitors; Circuit testing; Frequency; Insulation testing; Insulator testing; Power cables; System testing; Underground power cables; Voltage;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Electrical Insulation and Dielectric Phenomena, 1997. IEEE 1997 Annual Report., Conference on
  • Conference_Location
    Minneapolis, MN
  • Print_ISBN
    0-7803-3851-0
  • Type

    conf

  • DOI
    10.1109/CEIDP.1997.634626
  • Filename
    634626