DocumentCode
2086530
Title
Analyse on Relay Maloperation of Assembling Capacitor Bank for Internal Fault Protection
Author
Ma, Liang ; Xiong, Junjie ; Qian, Luojiang ; Liu, Yong
Author_Institution
Dept. of Power Syst., Jiangxi Electr. Power Res. Inst., Nanchang, China
fYear
2010
fDate
28-31 March 2010
Firstpage
1
Lastpage
4
Abstract
In this paper, internal fault protective relay maloperation of assembling capacitor bank caused by switching-on transient harmonics is analyzed. Mathematical expressions describing the adaptive settings of single-wye, dual-wye and bridge connections are given. The realistic action of internal fault protections under high amplitude harmonic conditions is possibly very different from theoretic setting. Major impact of harmonic is to change the maximum allowed fault units in the capacitor banks on which the relay action settings are tight depend. The paper deduces this change under harmonic condition and actual investigation results corroborate the rationality of the research work. Corresponding measure against the relay maloperation is discussed.
Keywords
capacitor switching; harmonic analysis; power system faults; power system harmonics; power system protection; power system relaying; relay protection; switching transients; transient analysis; bridge connections; capacitor bank; harmonic condition; high amplitude harmonic conditions; internal fault protective relay maloperation analysis; relay action; transient harmonics; Assembly systems; Bridge circuits; Capacitors; Power system protection; Power system relaying; Power system transients; Protective relaying; Reactive power; Shunt (electrical); Substation protection;
fLanguage
English
Publisher
ieee
Conference_Titel
Power and Energy Engineering Conference (APPEEC), 2010 Asia-Pacific
Conference_Location
Chengdu
Print_ISBN
978-1-4244-4812-8
Electronic_ISBN
978-1-4244-4813-5
Type
conf
DOI
10.1109/APPEEC.2010.5448167
Filename
5448167
Link To Document