• DocumentCode
    2095803
  • Title

    Fast and accurate measurement of power system frequency

  • Author

    Abu-El-Haija, Ahmad I.

  • Author_Institution
    Jordan Univ. of Sci. & Technol., Irbid, Jordan
  • Volume
    2
  • fYear
    2000
  • fDate
    2000
  • Firstpage
    941
  • Abstract
    A simple, fast and accurate method is presented for the measurement of the power system frequency. The method is based upon counting the number of strips (or samples) between zero crossings during one complete cycle of the sinusoidal waveform. Since the number of strips is usually not an integer, an estimate is derived that is very close to the actual value. The frequency is directly calculated front the number of strips. The measurement can be performed in at most 25 ms for a 60-Hz frequency, and at most 30 ms for a 50-Hz frequency. If the sinusoidal signal is sampled at 8 kHz for the purpose of measurement, the proposed method achieves accuracy in measuring the frequency of about 0.0001-0.0004 Hz
  • Keywords
    frequency measurement; power system measurement; signal sampling; waveform analysis; 50 Hz; 60 Hz; fast accurate measurement; harmonic distortion effect; noise effect; number of strips; operational frequency; power system frequency measurement; sample interval; sinusoidal waveform; zero crossings; Estimation error; Frequency estimation; Frequency measurement; Power generation; Power measurement; Power system measurements; Power system stability; Power systems; Signal to noise ratio; Strips;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Instrumentation and Measurement Technology Conference, 2000. IMTC 2000. Proceedings of the 17th IEEE
  • Conference_Location
    Baltimore, MD
  • ISSN
    1091-5281
  • Print_ISBN
    0-7803-5890-2
  • Type

    conf

  • DOI
    10.1109/IMTC.2000.848870
  • Filename
    848870