    Fault Location for 10kV Distribution Line Based on Traveling Wave - DC Theory

  • Author

    Guo, Zengwei ; Yan, Feng

  • Author_Institution
    Electr. Eng. Dept., North China Electr. Power Univ., Beijing, China
  • fYear
    2010
  • fDate
    28-31 March 2010
  • Firstpage
    1
  • Lastpage
    3
  • Abstract
    In this paper, the traditional fault location methods are analyzed, especially the C-type traveling wave location method; and a new composite method was presented which is based on traveling wave DC theory. The new method integrates the C-type of traveling wave location method with DC signal injection one. The aim is to combine different location methods to improve the accuracy of fault location. The new fault location method has two steps, the first step is determining the fault distance accurately by C-type of traveling wave location method; the second one is locating the fault branch by DC signal injection method. After theoretical analysis, ATP simulation, the composite location method is irrelevant to limits of the network dissymmetry, distributed capacitance and line parameter, can accurately determine the distribution network single-phase-to-earth fault location.
  • Keywords
    fault location; power distribution faults; power distribution lines; ATP simulation; C-type traveling wave location method; DC signal injection method; DC theory; distribution line; distribution network; fault location; voltage 10 kV; Analytical models; Capacitance; Detectors; Electronic mail; Fault detection; Fault location; Impedance measurement; Power system reliability; Signal analysis; Signal detection;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Power and Energy Engineering Conference (APPEEC), 2010 Asia-Pacific
  • Conference_Location
    Chengdu
  • Print_ISBN
    978-1-4244-4812-8
  • Electronic_ISBN
    978-1-4244-4813-5
  • Type

    conf

  • DOI
    10.1109/APPEEC.2010.5448924
  • Filename
    5448924