DocumentCode :
2106383
Title :
PD-source recognition in generator bars using a high-voltage coaxial-type high-pass filter
Author :
Naghashan, M.R. ; Zareie, H. ; Anvarifar, B.
Author_Institution :
Power & Water Univ. of Technol., Tehran
fYear :
2007
fDate :
22-24 Oct. 2007
Firstpage :
35
Lastpage :
38
Abstract :
A high-voltage coaxial-type high-pass filter is reconstructed and used to detect different impulse forms in generator bars. The test results of an old generator bar shows simultaneous occurrence of different discharge impulse forms. In this paper, the error of the band-pass filter used for PD measurement in delaminated aged bars is presented. It is essential to measure both discharge magnitude and discharge pulse forms to minimize the error.
Keywords :
band-pass filters; electric generators; high-pass filters; partial discharge measurement; power filters; PD-soourcerce recognition; band-pass filter; discharge impulse forms; generator bars; high-voltage coaxial-type high-pass filter; partial discharge measurement; Band pass filters; Bandwidth; Bars; Charge measurement; Circuit testing; Coaxial components; Current measurement; Partial discharges; Pulse measurements; Shape; Impulse form; delamination; generator bar; high-pass filter; partial discharge;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Electrical Insulation Conference and Electrical Manufacturing Expo, 2007
Conference_Location :
Nashville, TN
Print_ISBN :
978-1-4244-0446-9
Electronic_ISBN :
978-1-4244-0447-6
Type :
conf
DOI :
10.1109/EEIC.2007.4562583
Filename :
4562583
Link To Document :
بازگشت