DocumentCode :
2107367
Title :
Using COMTRADE records to test protective relays
Author :
Turner, Steve
Author_Institution :
Beckwith Electric Company
fYear :
2012
fDate :
2-5 April 2012
Firstpage :
401
Lastpage :
409
Abstract :
This purpose of this paper is to demonstrate how to use COMTRADE records to commission protective relays. COMTRADE records that have been captured by numerical relays and digital fault records during actual system events are of particular interest since these provide the ability to test protection for critical faults or disturbances such as an out of-step condition that are difficult to create using off the shelf test set software. Utilities and other customers can build a library of test cases. This paper shows how to use COMTRADE records to test transformer differential protection, loss of field protection and out-of step protection.
Keywords :
fault diagnosis; numerical analysis; relay protection; COMTRADE records; commission protective relays; critical faults; digital fault records; field protection; numerical relays; off the shelf test set software; out-of step protection; protective relays testing; transformer differential protection; Current transformers; Harmonic analysis; Impedance; Relays; Software; Surge protection; Surges;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Protective Relay Engineers, 2012 65th Annual Conference for
Conference_Location :
College Station, TX
Print_ISBN :
978-1-4673-1840-2
Type :
conf
DOI :
10.1109/CPRE.2012.6201248