• DocumentCode
    2114142
  • Title

    Current harmonic minimization of a grid-connected photovoltaic 500kW three-phase inverter using PR control

  • Author

    Song, Byeong-Mun ; Kim, Youngroc ; Cha, Hanju ; Lee, Hakju

  • Author_Institution
    Dept. of Electr. & Comput. Eng., Baylor Univ., Waco, TX, USA
  • fYear
    2011
  • fDate
    17-22 Sept. 2011
  • Firstpage
    1063
  • Lastpage
    1068
  • Abstract
    This paper presents a new current control strategy to minimize the current harmonics of a photovoltaic (PV) 500kW three-phase inverter using a proportional resonant (PR) controller. The new PR current control strategy is developed and implemented to a grid-connected three-phase inverter with LC filter. The controller resulted in a low current total harmonics distortion (THD) of 3% to meet the grid requirement. For the validation, simulation and experimental results showed that the proposed PR controller achieved a low THD over a wide range of operation under 500kW power flow. The detail design of the proposed controller is presented.
  • Keywords
    electric current control; harmonic distortion; harmonics suppression; invertors; photovoltaic power systems; power filters; power generation control; power grids; LC filter; PR current control strategy; current harmonic minimization; grid-connected photovoltaic three-phase inverter; low current total harmonics distortion; power 500 kW; proportional resonant controller; Current control; Harmonic analysis; Inverters; Power harmonic filters; Resonant frequency; Vectors; Voltage control;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Energy Conversion Congress and Exposition (ECCE), 2011 IEEE
  • Conference_Location
    Phoenix, AZ
  • Print_ISBN
    978-1-4577-0542-7
  • Type

    conf

  • DOI
    10.1109/ECCE.2011.6063891
  • Filename
    6063891