  • Abstract
    In the resonant-grounded distribution network, series resonance between the Peterson coil and the network zero-sequence capacitance after an arc incident presents great danger to the safe operation of the network. The key to solve this problem is to identify the exact arc extinguishing time. Based on the principles of transformer-based arc suppression coil (TASC), this paper introduces an arc extinguishing timing identification method, namely, frequency track method (FTM). The relationships between the thyristor´s triggering angle of the TASC and the frequency of the neutral point voltage is utilized in this proposed method. Laboratory and field tests have been carried out to verify the proposed method.
  • Keywords
    arcs (electric); earthing; power distribution protection; power transformers; thyristors; Peterson coil; TASC; arc extinguishing timing identification method; arc incident; distribution network safety; frequency track method; grounding status; network zero-sequence capacitance; thyristor; transformer-based arc suppression coil; Circuit faults; Coils; Fault currents; Frequency; Grounding; Inductance; RLC circuits; Resonance; Timing; Voltage;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Power and Energy Engineering Conference (APPEEC), 2010 Asia-Pacific
  • Conference_Location
    Chengdu
  • Print_ISBN
    978-1-4244-4812-8
  • Electronic_ISBN
    978-1-4244-4813-5
  • Type

    conf

  • DOI
    10.1109/APPEEC.2010.5449273
  • Filename
    5449273