  • Abstract
    The paper proposes a control algorithm for an integrated inverter system to maintain desired output voltage waveform when Power Quality disturbances occur. Most reason for these events are an instantaneous voltage sag and a momentary interruption. To solve these problem, when the power source voltage is out of normal range or a momentary power outage causes the problem, power is supplied to load through inverter stored in the battery voltage. Until they recover from the previous problem occurred, this proposed control method has little steady-state error, and good transient response characteristic. If power source voltage is supplying normal range, it operates based on current-controlled (APF mode). But if source voltage is supplying sag and momentary interruption, it operates based on voltage-controlled (UPS mode) that is supplying continuous voltage to load. During the UPS operation, when the source voltage returns to the normal range, it operates as an APF. In this paper proposed method has the advantage of the lower cost and smaller space, major automation equipment protects from a momentary interruption and sag of within one second, and this system designed sinusoidal that output waveform. In this paper System Control (APF, Boost Vdc, Mode Conversion) will discuss.
  • Keywords
    active filters; invertors; load (electric); power conversion; power filters; power supply quality; power system protection; transient response; uninterruptible power supplies; voltage control; UPS-APF power conversion equipment; active power filter; automation equipment protection; battery voltage; continuous voltage supply; current-controlled mode; instantaneous voltage sag; integrated inverter system control algorithm; momentary interruption; momentary power outage; power quality disturbance; power source voltage; seamless mode transfer; steady-state error; transient response; uninterruptible power supply; voltage waveform; voltage-controlled mode; Active filters; Harmonic analysis; Power harmonic filters; Reactive power; Uninterruptible power systems; Voltage control; Voltage fluctuations; APF; Seamless Mode Transfer; UPS;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Power Electronics and ECCE Asia (ICPE & ECCE), 2011 IEEE 8th International Conference on
  • Conference_Location
    Jeju
  • ISSN
    2150-6078
  • Print_ISBN
    978-1-61284-958-4
  • Electronic_ISBN
    2150-6078
  • Type

    conf

  • DOI
    10.1109/ICPE.2011.5944770
  • Filename
    5944770