Abstract :
Winding deformation is one of the most common faults of power transformers. It may cause partial discharge, even leads to insulation breakdown. Winding deformation also may cause the decreasing of mechanical properties of winding. The study of high sensitive detection method has important significance for detecting minimal change of transformer winding. So authors propose utilizing the nanosecond pulse method to detect winding deformation. Through computer simulations, the parameters of the nanosecond pulse is studied intensively in this paper. By means of analysis, a impulse that has a wave front 5 ns ± 30% and impulse width 50 ns ± 30% has been defined as signal source. To verify the effectiveness of the method, a testing power transformer was detected with the way of the nanosecond pulse. Testing results may reflected winding deformation very well. At the same time, the repeatability is good at the frequency range from 0 to 80 MHz..
Keywords :
power transformer testing; transformer windings; computer simulations; frequency 0 MHz to 80 MHz; nanosecond pulse method; power transformer faults; transformer winding deformation detection; Computer simulation; Electric breakdown; Mechanical factors; Partial discharges; Power transformer insulation; Power transformers; Pulse transformers; Signal analysis; Testing; Windings;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Power and Energy Engineering Conference (APPEEC), 2010 Asia-Pacific
Conference_Location :
Chengdu
Print_ISBN :
978-1-4244-4812-8
Electronic_ISBN :
978-1-4244-4813-5
Type :
conf
DOI :
10.1109/APPEEC.2010.5449342
Filename :
5449342
Link To Document :
بازگشت