DocumentCode
2118817
Title
Voltage Supporting Strength Evaluation Of The HVDC Receiving Grid In Synchronous And Asynchronous Interconnecting Power System
Author
Su Yue-ping ; Guan Lin
Author_Institution
Sch. of Electr. Power, South China Univ. of Technol., Guangzhou, China
fYear
2010
fDate
28-31 March 2010
Firstpage
1
Lastpage
4
Abstract
This paper simulates the voltage sags caused by HVDC failures in both the asynchronous interconnecting and the AC/DC parallel power systems and studies their relationships with the short circuit ratio (SCR) series indices. It´s found that in the asynchronously interconnected power system the SCR indices can quantitatively indicate the voltage supporting ability of the receiving-end AC system under HVDC failures. However in the AC/DC parallel system the SCR indices are ineffective. An improved SCR index is then proposed to solve the problem. Simulations prove its feasibility in the AC/DC parallel power systems.
Keywords
fault diagnosis; power grids; power supply quality; power system interconnection; AC-DC parallel power systems; HVDC receiving grid; asynchronous interconnecting power system; short circuit ratio series indices; synchronous interconnecting power system; voltage sags; voltage supporting strength evaluation; Circuit faults; HVDC transmission; Integrated circuit interconnections; Power grids; Power system faults; Power system interconnection; Power system modeling; Power system simulation; Thyristors; Voltage;
fLanguage
English
Publisher
ieee
Conference_Titel
Power and Energy Engineering Conference (APPEEC), 2010 Asia-Pacific
Conference_Location
Chengdu
Print_ISBN
978-1-4244-4812-8
Electronic_ISBN
978-1-4244-4813-5
Type
conf
DOI
10.1109/APPEEC.2010.5449452
Filename
5449452
Link To Document