    Voltage Supporting Strength Evaluation Of The HVDC Receiving Grid In Synchronous And Asynchronous Interconnecting Power System

  • Author

    Su Yue-ping ; Guan Lin

  • Author_Institution
    Sch. of Electr. Power, South China Univ. of Technol., Guangzhou, China
  • fYear
    2010
  • fDate
    28-31 March 2010
  • Firstpage
    1
  • Lastpage
    4
  • Abstract
    This paper simulates the voltage sags caused by HVDC failures in both the asynchronous interconnecting and the AC/DC parallel power systems and studies their relationships with the short circuit ratio (SCR) series indices. It´s found that in the asynchronously interconnected power system the SCR indices can quantitatively indicate the voltage supporting ability of the receiving-end AC system under HVDC failures. However in the AC/DC parallel system the SCR indices are ineffective. An improved SCR index is then proposed to solve the problem. Simulations prove its feasibility in the AC/DC parallel power systems.
  • Keywords
    fault diagnosis; power grids; power supply quality; power system interconnection; AC-DC parallel power systems; HVDC receiving grid; asynchronous interconnecting power system; short circuit ratio series indices; synchronous interconnecting power system; voltage sags; voltage supporting strength evaluation; Circuit faults; HVDC transmission; Integrated circuit interconnections; Power grids; Power system faults; Power system interconnection; Power system modeling; Power system simulation; Thyristors; Voltage;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Power and Energy Engineering Conference (APPEEC), 2010 Asia-Pacific
  • Conference_Location
    Chengdu
  • Print_ISBN
    978-1-4244-4812-8
  • Electronic_ISBN
    978-1-4244-4813-5
  • Type

    conf

  • DOI
    10.1109/APPEEC.2010.5449452
  • Filename
    5449452