DocumentCode :
2120706
Title :
Design of a low voltage cable fault detector
Author :
Potivejkul, S. ; Kerdonfag, P. ; Jamnian, S. ; Kinnares, V.
Author_Institution :
Fac. of Eng., King Mongkut´´s Inst. of Technol., Bangkok, Thailand
Volume :
1
fYear :
2000
fDate :
2000
Firstpage :
724
Abstract :
This paper presents a design and construction of a low voltage cable fault location detector. The principle of design is based on the reflection of waves. A pulse is sent into the defective cable and it is reflected back. The interval of travelling waves is identified in order to determine fault location and fault types. The prototype consists of pulse generator, wave detection circuit, counter circuit, control and processing part, and display unit based on a microcontroller. All are assembled in a small compact size. Also, the portable detector is suitable for outdoors. In addition, it is more safe when compared to a conventional high voltage impulse method. It has been tested and found that the error of fault location is within ±5%
Keywords :
electromagnetic wave reflection; fault location; impulse testing; microcontrollers; power cable testing; pulse generators; waveform analysis; counter circuit; defective cable; display unit; fault location; fault types determination; low voltage cable fault detector; microcontroller; outdoors; portable detector; pulse generator; pulse reflection; travelling waves interval; wave detection circuit; wave reflection; Circuit faults; Detectors; Electrical fault detection; Fault detection; Fault diagnosis; Fault location; Low voltage; Prototypes; Pulse generation; Reflection;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Power Engineering Society Winter Meeting, 2000. IEEE
Print_ISBN :
0-7803-5935-6
Type :
conf
DOI :
10.1109/PESW.2000.850153
Filename :
850153
Link To Document :
بازگشت