Breaking performance of a capacitive-graded series design of two 24-kV vacuum circuit breakers
Author
Fugel, Thorsten ; Koenig, Dieter
Author_Institution
High Voltage Lab., Darmstadt Univ. of Technol., Germany
fYear
2002
fDate
2002
Firstpage
360
Lastpage
363
Abstract
This contribution deals with the breaking capability of a series design consisting of two 24-kV vacuum circuit breakers (VCB) with grading capacitors. In previous publications it was shown that the breaking capability of the series arrangement is higher compared to the double of a single tube. In addition to these results it is shown that in some cases grading capacitors can increase the breaking capacity even more. Tests with simultaneous opening of the contacts of both tubes are presented with the application of different grading capacitors as well as the choice of different arcing times. In case of reignition of one of the tubes the current circulating between the two tubes is shown. As a result of the tests the breaking capability of the arrangement depending on the arcing time and the value of the grading capacitors can be classified into three zones: area of reignition of the arrangement, scatter area and area of successful arc quenching.
Keywords
circuit-breaking arcs; power capacitors; switchgear testing; vacuum arcs; vacuum circuit breakers; 24 kV; arcing times; breaking capacity; breaking performance; capacitive-graded series design; circulating current; reignition; scatter area; simultaneous contacts opening; successful arc quenching area; vacuum circuit breakers; Actuators; Capacitors; Circuit breakers; Circuit testing; Electromagnetic measurements; Transient analysis; Vacuum arcs; Vacuum systems; Vacuum technology; Voltage;
fLanguage
English
Publisher
ieee
Conference_Titel
Discharges and Electrical Insulation in Vacuum, 2002. 20th International Symposium on
Print_ISBN
0-7803-7394-4
Type
conf
DOI
10.1109/ISDEIV.2002.1027383
Filename
1027383
Link To Document