    Dielectric strength of the vacuum interrupter sections after termination of the electric life

  • Author

    Rylskaya, L.

  • Author_Institution
    All-Russian Electrotechnical Inst. (VEI), Moscow, Russia
  • fYear
    2002
  • fDate
    2002
  • Firstpage
    376
  • Lastpage
    379
  • Abstract
    The dielectric strength of the vacuum interrupter (VI) sections is studied after termination of the electric life. It is shown the reduction of the electric life occurs in particular cases and its reason is the appearance of more low voltage breakdowns called as "slow" because of increasing almost by an order the time of the voltage drop to zero during breakdown (several microseconds against fractions of a microsecond for breakdowns in new vacuum interrupters). The conditions of occurrence of such "slow" breakdowns are considered.
  • Keywords
    electric strength; switchgear testing; vacuum breakdown; vacuum interrupters; 1250 A; 20 kA; 35 kV; dielectric strength; electric life reduction; electric life termination; low voltage breakdowns; slow breakdowns; vacuum interrupter; voltage drop to zero; Breakdown voltage; Circuit testing; Dielectric breakdown; Dielectrics and electrical insulation; Electric breakdown; Interrupters; Laboratories; Lightning; Vacuum arcs; Vacuum breakdown;